YDY 450/750V Cable - Pektas Cable
FLAT AND CIRCULAR CABLES

YDY 450/750V Cable

It is used in embedded conduits and switchboards.
Max. operating temperature
70 °C
Max. short circuit temperature
160 °C
Min. storage temperature
-40 °C
AC test voltage
2.5 kV
Min. bending radius
8 x D
Rated voltage Uo/U
450/750 V
Flame propagation test on single cable
EN 60332-1-2

Construction

  • 1- Conductor: Solid copper
  • 2- Insulation: Polyvinyl chloride (PVC)
  • 3- Outer Sheath: Polyvinyl chloride (PVC)

Applications

It is used in embedded conduits and switchboards.

Technical Data - YDY 450/750V

Nominal Cross Section mm²Overall Diameter mmNet Weight kg/kmConductor DC Resistance at (20°C) max. ohm/kmCurrent Carrying Capacity in Air (A)
2x17.58118.1-
2x1.589712.115
2x2.58.81257.4120
2x410.11764.6127
2x611.12283.0834
3x17.99618.1-
3x1.58.511612.115
3x2.59.31537.4120
3x410.72194.6127
3x6122943.0834
4x18.611618.1-
4x1.59.214212.115
4x2.510.11907.4120
4x411.92794.6127
4x613.13693.0834
4x10165811.8346
5x19.113618.1-
5x1.59.716812.115
5x2.510.72277.4120
5x412.63354.6127
5x613.94473.0834
5x10177071.8346