VO-YMvKas Fire Safe Armored Power Cable - Pektas Cable

VO-YMvKas

It is used in buildings with high human density, hospitals, shopping malls, hotels, schools, etc. It does not propagate fire, does not create thick smoke, and does not create an environment suitable for corrosion during a fire. The galvanized round steel wire and tapes on it provide extremely good protection against mechanical stresses.
Max. operating temperature
90 °C
Max. short circuit temperature
250 °C
AC test voltage
3.5 kV
Min. bending radius
15 x D
Rated voltage Uo/U
0.6/1 kV
Flame propagation test on single cable
EN 60332-1-2
Flame propagation test on bunched cables
EN 60332-3-24
Corrosive gas test
EN 60754-2
Smoke density test
EN 61034-2

Construction

  • 1- Conductor: Solid or stranded copper
  • 2- Insulation: Cross-linked polyethylene (XLPE)
  • 3- Filler: Halogen-free lshz material
  • 4- Armor: Galvanized steel / aluminum round wires with stranded insulated copper protection wire underneath
  • 5- Outer Sheath: Halogen-free lshz compound

Applications

It is used in buildings with high human density, hospitals, shopping malls, hotels, schools, etc. It does not propagate fire, does not create thick smoke, and does not create an environment suitable for corrosion during a fire. The galvanized round steel wire and tapes on it provide extremely good protection against mechanical stresses.

Technical Data - VO-YMvKas

Nominal Cross Section mm²Overall Diameter mmNet Weight kg/kmConductor DC Resistance at (20°C) Max. ohm/kmCurrent Carrying Capacity in Ground (A)Current Carrying Capacity in Air (A)
2x1,5+1,512,423812,124
2x2,5+2,513,22517,4132
2x4+414,03614,6142
2x6+617,54503,0853
3x1,5+1,512,421612,124
3x2,5+2,513,22937,4132
3x4+415,54254,6142
3x6+619,25353,0853
4x1,5+1,513,532112,124
4x2,5+2,514,43347,4132
4x4+415,54444,6142
4x6+619,25743,0853