Halogen Free Flame Retardant Flat Cable - Pektas Cable
FLAT AND CIRCULAR CABLES

624-B

Used as surface wiring where there is little mechanical damage risk, or in conduit. Low level of smoke emission and corrosive gasses in case of fire.
Max. operating temperature
90 °C
Max. short circuit temperature
250 °C
AC test voltage
2kV
Min. bending radius
8 x D
Rated voltage Uo/U
300/500 V
Flame propagation test on single cable
EN 60332-1
Halogen free
EN 50525-1 - EN 50267
Low smoke
EN 61034

Construction

  • 1- Solid or stranded copper (Class 1 or Class 2)
  • 2- Cross linkable polyethylene
  • 3- Low smoke zero halogen

Applications

Used as surface wiring where there is little mechanical damage risk, or in conduit. Low level of smoke emission and corrosive gasses in case of fire.

Technical Data - 624-B (300/500 V) / Cu/XLPE/LSZH

Nominal Cross Section mm²Mean Overall Dimension mm (Lower Limit / Upper Limit)Net Weight kg/kmConductor DC Resistance at (20°C) max. ohm/kmCurrent Carrying Capacity in Air (A)
1x1+1 re4.1x5.2 / 5.0x6.34218.1/18.117
1x1.5+1 re4.4x5.4 / 5.3x6.64812.1/18.123
2x1+1 re4.1x7.6 / 5.0x9.16518.1/18.117
2x1+1 rm4.2x7.8 / 5.1x9.46518.1/18.117
2x1.5+1 re4.4x8.1 / 5.3x9.77612.1/18.123
2x1.5+1 rm4.5x8.3 / 5.4x10.07612.1/18.123
2x2.5+1.5 re4.9x9.3 / 6.0x11.21087.41/12.131
2x2.5+1.5 rm5.0x9.5 / 6.1x11.41087.41/12.131
2x4+1.5 rm5.5x10.4 / 6.7x12.61484.61/12.142
2x6+2.5 rm6.2x12.0 / 7.5x14.62083.08/7.4154
2x10+4 rm7.3x14.5 / 8.8x17.63171.83/4.6175
2x16+6 rm8.4x17.0 / 10.1x20.54781.15/3.08100
3x1+1 re4.1x10.0 / 5.1x12.18718.1/18.117
3x1.5+1 re4.4x10.7 / 5.3x12.910412.1/18.123
3x2.5+1 re4.9x12.0 / 6.0x14.61427.41/18.131
3x4+1.5 rm5.5x14.0 / 6.7x16.92074.61/12.142
3x6+2.5 rm6.2x16.2 / 7.5x19.52913.08/7.4154
3x10+4 rm7.3x19.5 / 8.8x23.64421.83/4.6175
3x16+6 rm8.4x22.8 / 10.1x27.66711.15/3.08100