H07V-R PVC Insulated Installation Cables - Pektas Cable
INSULATED WIRES

H07V-R (PVC Insulated Installation Cables)

Installation in dry premises, switchboards, and distribution boards, in surface mounted or embedded conduits.
Max. operating temperature
70 °C
Max. short circuit temperature
160 °C
AC test voltage
2.5 kV
Min. bending radius
D<8 is 4xD, 8≤D≤12 is 5xD, D>12 is 6xD
Rated voltage Uo/U
450/750 V
Flame propagation test on single cable
EN 60332-1-2

Construction

  • 1- Conductor: Stranded copper
  • 2- Insulation: Polyvinyl chloride (PVC)

Applications

Installation in dry premises, switchboards, and distribution boards, in surface mounted or embedded conduits.

Technical Data - H07V-R (450/750V) / 6491X

Nominal Cross Section mm²Overall Diameter mmNet Weight kg/kmConductor DC Resistance at (20°C) max. ohm/kmCurrent Carrying Capacity in Conduit (A)Current Carrying Capacity in Air (A)
1.53.02112.114.524
2.53.6327.4119.532
44.2484.612642
64.8673.083454
105.91101.834673
166.91811.156198
258.22800.72780129
359.33820.52499158
5010.85420.387119198
7012.47450.268151245
9514.510100.193182292
12015.912600.153210344
15017.715750.124240391
18519.819450.0991273448
24022.825200.0754320528
30025.229500.0601--
40031.237400.0470--
50035.648200.0366--
60037.661450.0283--