EXVB Unarmored Power Cable - Pektas Cable
UNARMOURED ENERGY CABLES

EXVB

It is used outdoors, indoors, underground and in cable ducts where there are no severe mechanical stresses.
Max. operating temperature
90 °C
Max. short circuit temperature
250 °C
AC test voltage
3.5 kV
Min. bending radius
12 x D
Rated voltage Uo/U
0.6/1 kV
Flame propagation test on single cable
EN 60332-1-2

Construction

  • 1- Conductor: Solid or stranded copper
  • 2- Insulation: Cross-linked polyethylene (XLPE)
  • 3- Filler: Polyvinyl chloride (PVC) (Only for multi-core cables)
  • 4- Outer Sheath: Polyvinyl chloride (PVC) or PE

Applications

It is used outdoors, indoors, underground and in cable ducts where there are no severe mechanical stresses.

Technical Data - EXVB

Nominal Cross Section mm²Overall Diameter mmNet Weight kg/kmConductor DC Resistance Max. ohm/km(20°C)Current Carrying Capacity (In Earth)Current Carrying Capacity (In Air)
Flat Trefoil Flat Trefoil
1x1,56,155412,1-23--
1x2,56,54667,413431--
1x47,01844,6166545640
1x67,511063,0882677953
1x108,851571,831098910174
1x169,802181,15139115137101
1x2511,403200,727179148182135
1x3512,504180,524213177226169
1x5014,205550,387251209275207
1x7015,907640,268307256353268
1x9517,8010190,193366307430328
1x12019,7012690,153416349500383
1x15021,4015480,124465393577444
1x18523,4019070,0991526445661510
1x24026,6024710,0754610517781607
1x30028,8031240,0601927663901697
1x40034,039390,047010647491060811
1x50039,950730,036611278431252940
3x1,511,9019412,13023
3x2,512,902427,414032
3x413,803054,615042
3x614,903823,086554
3x1017,405571,839075
3x1619,607741,15120100
3x2522,9011300,727150127
3x3525,4014780,524175157
4x1,512,8022912,13023
4x2,513,702827,414032
4x414,803654,615042
4x616,004623,086554
4x1018,806831,839075
4x1621,309621,15120100
4x2525,0014170,727150127
4x3527,7018590,524175157
5x1,513,5025912,13023
5x2,514,603277,414032
5x415,804284,615042
5x617,105453,086554
5x1020,08081,839075
5x1623,0011601,15120100
5x2527,2017280,727150127
5x3530,3022820,524175157