Cold Resistant, Single Core Cables - Pektas Cable
INSULATED WIRES

H07V3_R

Installation in surface mounted or embedded conduits or similar closed systems at low temperatures.
Max. operating temperature
70 °C
Max. short circuit temperature
160 °C
AC test voltage
2.0 kV, 2.5 kV
Min. bending radius
D<8 is 4xD, 8≤D≤12 is 5xD, D>12 is 6xD
Rated voltage Uo/U
300/500 V, 450/750 V
Flame propagation test on single cable
IEC 60332-1

Construction

  • 1- Solid or stranded copper (Class 1 or Class 2)
  • 2- Cold resistant polyvinyl chloride

Applications

Installation in surface mounted or embedded conduits or similar closed systems at low temperatures.

Technical Data - H05V3-U (300/500 V) & H07V3-U / H07V3-R (450/750 V) / Cu/CR-PVC

Nominal Cross Section mm²Overall Diameter mmNet Weight kg/kmConductor DC Resistance at (20°C) max. ohm/kmCurrent Carrying Capacity in Conduit (A)Current Carrying Capacity in Air (A)
0.52.0936.0--
0.752.21224.5-15
12.31518.11119
1.52.82012.11625
2.53.3307.412134
43.8454.612745
64.3653.083557
106.01151.834878
167.01701.1565104
258.52600.72788137
359.53600.524110168
5011.04800.387140210
7013.06700.268175260
9515.09300.193210310
12016.511600.153250365
15018.014200.124-415
18520.017800.0991-475
24023.023300.0754-560
30026.029300.0601-645
40029.037500.0470-770