XLPE Insulated, Halogen Free, Multi-Core Flexible Cables - Pektas Cable
FLEXIBLE CABLES

052XZ1-F

Used in refineries, hotels, schools, tunnels, high constructions, hospitals, power plants, data processing centers, populated business centers where there is a risk of fire.
Max. operating temperature
90 °C
Max. short circuit temperature
250 °C
AC test voltage
2kV
Min. bending radius
D≤12 is 5 x D, D>12 is 6 x D
Rated voltage Uo/U
300/500 V
Flame retardant test of Bundled cables
EN 60332-3-24 Cat.C
Halogen free
EN 50525-1 / EN 50267
Low smoke
EN 61034

Construction

  • 1- Fine-stranded copper (Class 5)
  • 2- Cross linkable polyethylene
  • 3- Low smoke halogen free

Applications

Used in refineries, hotels, schools, tunnels, high constructions, hospitals, power plants, data processing centers, populated business centers where there is a risk of fire.

Technical Data - 052XZ1-F (300/500 V) / Cu/XLPE/LSZH

Nominal Cross Section mm²Overall Diameter mmNet Weight kg/kmConductor DC Resistance at (20°C) max. ohm/kmCurrent Carrying Capacity in Air (A)
2x0.756.15526.06
2x16.66519.510
2x1.58.310313.316
2x2.510.31637.9825
2x410.31844.9532
3x0.756.56326.06
3x17.07719.510
3x1.58.411313.316
3x2.59.81647.9825
3x411.12244.9532
4x0.757.78126.06
4x17.79719.510
4x1.59.414113.316
4x2.510.61937.9825
4x412.02804.9532
5x0.757.99926.06
5x18.711719.510
5x1.59.615413.316
5x2.512.02307.9825
5x413.23204.9532